Industrial Inverter (7.5KVA - 10KVA)

Industrial Inverter (7.5KVA - 10KVA)

FEATURES

 
  • Hybrid Design (Grid & Solar Charging)
  • Inbuilt intelligent charge controller
  • High Efficiency Design
  • Superior Algorithm
  • Solar priority / Grid Priority Logic
  • Electronic Protection
  • Auto restart facility
  • LCD Display
  • Inbuilt Measurements 
  • Compact / Rugged design
  • Remote monitoring facility (Optional)
 

Specification

MODEL IG7500VA IG10000VA
Capacity (VA) 7500 10000
Capacity (W) 6000 8000
Battery VDC 120 192
Nominal Output Voltage 220 - 240VAC
INPUT
User Selection Mode UPS MODE / INVERTER MODE
Voltage Range 180 – 256V AC / 110 – 290V AC
Voltage Cut off Range 180 – 265 ± 5 V AC / 110 – 290 ± 10 V AC
Voltage Recovery Range 190 – 255 ± 5 V AC / 120 – 275 ± 10 V AC
Frequency Range 47 – 53 Hz
OUTPUT
Voltage Regulation on Mains Same as Mains Input
Voltage Regulation in Battery Mode 220V AC Nominal ± 2% (Range 210V – 240V)
Frequency Regulation on Mains Mode Same as Mains Input
Frequency Regulation in Battery Mode 50HZ ± 0.1 Hz
Power Factor  >0.8
Waveform Pure Sine Wave
Efficiency >85% 
Over Load (PCU Mode) 120% load on Inverter for 30 sec. ;  9000 12000
After 3 Retries and Shutdown. 8700 11600
Max  Load (Grid Mode) 10000 12000
Battery Charging -GRID
Grid Charging Current 50A 80A
Boost Charging’ voltage 144 ±0.2V
Float Charging’ voltage 138 ±0.2V
'Battery low voltage cut-off' 105 ±0.2 V
Battery Voltage High 162.5 ±0.2 V
SPV Charging - SOLAR
Charge controller Type MPPT (Maximum Power Point Tracking)
Maximum SPV Input Power 5000Wp 6000Wp
Nominal SPV input Voltage 150V 250
Max. PV  Input voltage (VOC) 200V 300
Panel Voltage Operation range 150 - 200V 250 - 300V
Max. Charging Current 40A 50A
PROTECTIONS
Over Load For 100% Load – Buzzer Indication, 101% above load trips & retry for 4 times then inverter shutdown
Output Short Circuit Circuit breaker on mains, Shutdown on inverter
Battery Reverse Protection  Fuse
Low Battery Load Disconnection
Thermal Shutdown Below 0°C and above 90°C
Lightening/Surge Protected up to 4KV Surge
Solar Reverse Blocking diode is provided to prevent reverse flow of current
Change Over Time <20ms
ENVIRONMENT OPERATING CONDITIONS
Operating Temperature 0 - 50°C
Storage Temperature 0 to +60 °C
Relative Humidity 0-95% non-condensing
Cooling Forced fan cooling
Altitude Less than 2000 meter above sea level
Communication Optional
DISPLAY
LED Display Mains ON(Red), Charging On Mains (RED), Charging On Solar(Green), Inverter(Green), Battery Low(Yellow), Overload/Short Circuit(Yellow)
LCD Display Battery Voltage,  Input Voltage Band (Narrow or Wide) , Grid Charging Current , Solar Voltage., Solar Charging Current, Solar Units Saved kWH, Over Load, Battery Low Indication.

Note:   *Specifications are subject to change without notice.

             * Image shown are just indicative